UNI 12845/20 pump group composed of electric pump, motor pump and pilot complete with electrical panels and various accessories always supplied on separate skids as per UNI 11292/19 standard
Electric fan for forced air exchange, functioning even in the absence of electricity, complete with UNI 11292 /19 point 5.4.2.2 grille.
REI60 front access door vertical type measures min. L 800 H 2000 and with fire reaction class A1 as per UNI 11292/19 point 4.2.2.
Pump intakes complete with anti-vortex plate filter, eccentric reduction cone, anti-vibration joint, shut-off butterfly valves and various connection flanges as per UNI 12845/20.
Electrical panel for the management of all services inside the technical compartment already wired and complete with circuit breakers and life-saving circuit breakers, all certified with Declaration of Conformity.
Inverter voltage rescuer complete with batteries to operate the electric fan (if one or more motor pumps are present) in the absence of electricity, UNI EN 11292/19 standard point 5.4.2.
Narrow mesh grating or ashlar sheet metal floor, uniform, non-slip, raised so that operators can move around safely, as required by UNI 11292 regulation.
Possibility of having the water delivery and tank loading pipes inside the technical compartment, thus eliminating problems related to the cold which would force the client to have to use insulation, heating cables, etc.